Skip to content
Control & signal

YSLYCY-JZ

PVC screened flexible control cable, 300/500 V

300/500 V CPR Eca Based on EN 50525-2-51
CU/PVC/TCWB/PVC On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

YSLYCY-JZ (also known as CY) is the screened version of YSLY-JZ: a tinned copper braid around the cores limits pick-up and emission. The right choice wherever the cable runs alongside drives or motors, or carries sensitive signals itself. The screen only works if you earth it correctly. Supplied to order; the lead time is stated in the quote.

YSLYCY-JZ (also known as CY) is a flexible multicore control cable with class 5 fine-wire plain copper conductors, PVC core insulation, a tinned copper wire braid screen and a PVC outer sheath, rated 300/500 V. The braid screen limits electromagnetic interference to and from the cable, making the type suitable for control, signalling and measuring circuits in machinery, plant and process installations where EMC requirements apply. It is intended for fixed installation and for occasional free movement without tensile load or forced guiding, in dry and damp indoor locations; the sheath is resistant to common oils and greases.

ScreenedEMCMachine building

Also known as: CY · YSLYCY-JB · screened control cable

Applications

  • Control and measuring circuits alongside drives, servos and large motors.
  • Machines and process installations with EMC requirements on the wiring.
  • Environments with oil and grease; the PVC sheath resists both.

What to look out for

  • With drives, earth the braid at both ends 360° through EMC glands; with a pigtail (a wire tail on the braid), the screen is largely ineffective at high frequencies.
  • CPR class Eca. Where the cable is installed permanently in a building and exposed to indoor air, the Bbl requires at least Dca. The wiring inside a control panel or machine is not covered by that requirement, but the cables running to it are.
Construction
Conductor
Fine-wire stranded plain (bare) copper, class 5 to IEC/EN 60228.
Insulation
PVC; cores laid up in layers.
Screen
Tinned copper wire braid over a PVC inner sheath.
Sheath
PVC outer sheath, grey or transparent.
Core identification
Black cores with white numbers to VDE 0293-334; green/yellow protective conductor in the outer layer from 3 cores upwards; 2-core numbered without green/yellow. Also available with coloured cores to HD 308 (JB/OB) on request.
Electrical & thermal properties
Rated voltage Uo/U
300/500 V.
Test voltage
2,000 V.
Standard
Based on EN 50525-2-51 (not harmonised).
Flame-retardant
IEC/EN 60332-1-2.
Conductor standard
IEC/EN 60228 class 5.
Max. conductor temperature
70 °C.
Permitted outer cable temperature, fixed
−20 °C to +70 °C.
Permitted outer cable temperature, flexing
+5 °C to +70 °C.
Min. bending radius, fixed
6 × outer diameter.
Min. bending radius, flexing
20 × outer diameter.
Reaction to fire (CPR)
Eca (EN 50575); as a flexible cable it falls outside CPR scope when used only for the connection of mobile equipment.
Dimensions and technical data

Sizes and weights

Cores × mm²R DC 20 °C (Ω/km)Outer Ø approx. (mm)Weight approx. (kg/km)
2×0.539767
3×0.5397.583
4×0.5397.994
5×0.5398.6108
6×0.5399.3125
7×0.5399.3136
8×0.5399.9150
10×0.53911.2170
12×0.53911.5195
14×0.53912.3223
16×0.53912.8250
18×0.53913.7277
20×0.53914.3310
21×0.53914.3331
24×0.53915.8390
25×0.53915.8407
30×0.53916.7520
32×0.53917.2550
36×0.53917.9585
40×0.53918.5654
41×0.53919.4671
50×0.53920.9740
61×0.53922.1850
80×0.53925.41080
100×0.53928.11350
2×0.75267.787
3×0.7526898
4×0.75268.9113
5×0.75269.5130
6×0.752610.1156
7×0.752610.1184
8×0.752610.9221
10×0.752612.6270
12×0.752613292
14×0.752613.8315
16×0.752614.4335
18×0.752615.2358
20×0.752616.2420
21×0.752616.2454
24×0.752617.7480
25×0.752617.7508
27×0.752617.7535
30×0.752618.5640
32×0.752619.5688
36×0.752620.1730
40×0.752620.9950
41×0.752621.5971
50×0.752623.61100
61×0.7526251290
80×0.752628.61510
100×0.752631.61640
2×119.5897
3×119.58.6103
4×119.59.3146
5×119.59.9169
6×119.510.7199
7×119.510.7219
8×119.511.8270
10×119.513.6330
12×119.514350
14×119.514.7400
16×119.515.3422
18×119.516.3514
20×119.517545
24×119.518.6640
25×119.518.6689
28×119.519.9710
30×119.519.9762
34×119.521.3910
40×119.522.21070
41×119.5231092
50×119.525.31315
61×119.526.91370
80×119.530.71610
100×119.533.91840
2×1.513.39130
3×1.513.39.4152
4×1.513.310168
5×1.513.310.9202
7×1.513.312304
8×1.513.313336
10×1.513.315420
12×1.513.315.4434
14×1.513.316.4480
16×1.513.317.1525
18×1.513.318640
20×1.513.319690
21×1.513.319720
24×1.513.321770
25×1.513.321805
28×1.513.322.2900
30×1.513.322.2950
35×1.513.3241100
40×1.513.3251350
41×1.513.325.91381
50×1.513.328.41675
61×1.513.330.21800
80×1.513.334.42300
100×1.513.338.42600
2×2.57.9810.4180
3×2.57.9810.9216
4×2.57.9812267
5×2.57.9812.9347
7×2.57.9814.2407
10×2.57.9818660
12×2.57.9818.5722
2×44.9512302
3×44.9512.6340
4×44.9513.9410
5×44.9515.2502
7×44.9516.6638
2×63.314350
3×63.314.9450
4×63.316.4559
5×63.317.9702
7×63.319.6907
2×101.9117500
3×101.9118.1750
4×101.9119.91020
5×101.91221115
7×101.91241500
4×161.2124.11380
5×161.2126.71553
4×250.7829.11890
5×250.7832.22270
4×350.55432.12390
5×350.55435.52885
4×500.38637.93315
5×500.386424150
4×700.272434600
5×700.27247.85750
4×950.20649.66060
5×950.20654.87580
4×1200.16154.67315
5×1200.16159.79150
4×1500.12959.89680
5×1500.12965.510170

Nominal values; conductor resistance is the maximum to IEC 60228, class 5. All values are indicative.

Which one do I choose?

YSLYCY-JZ or YSLYCY-OZ?

YSLYCY-JZ

  • green/yellow core from three cores

YSLYCY-OZ

  • no green/yellow core

Both are screened PVC control cables for 300/500 V with black, numbered cores and a tinned copper braid. YSLYCY-JZ has a green/yellow protective conductor from three cores up; YSLYCY-OZ does not. Choose YSLYCY-JZ if the protective conductor must be in the cable, and YSLYCY-OZ if earthing runs elsewhere or all cores carry signals.

View YSLYCY-OZ →

YSLYCY-JZ or H05VVC4V5-K?

YSLYCY-JZ

  • not harmonised

H05VVC4V5-K

  • harmonised, EN 50525-2-51

Both are screened PVC control cables for 300/500 V with a tinned copper braid. H05VVC4V5-K is harmonised to EN 50525-2-51, the standard for oil-resistant control cables. YSLYCY-JZ is not harmonised. Choose H05VVC4V5-K if the specification calls for a harmonised type or oil resistance to EN 50525-2-51; otherwise YSLYCY-JZ is enough.