NYY

PVC power / underground cable, 0.6/1 kV

0.6/1 kV CPR Eca DIN VDE 0276-603 (HD 603)
CU/PVC/PVC On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

NYY is the German PVC power and underground cable for 0.6/1 kV: copper, PVC insulation and a black PVC sheath, suitable for direct burial. The counterpart of YMvK and VO-YMvKas for projects to German specification. Supplied to order; the lead time is stated in the quote.

NYY (also (N)YY) is a PVC-insulated power and underground cable for a rated voltage of 0.6/1 kV to DIN VDE 0276-603 (HD 603 S1), with plain copper conductors (solid class 1 / stranded class 2, circular or sector-shaped), PVC core insulation, an inner PVC covering (bedding) and a black PVC outer sheath. It is used for fixed power distribution in buildings, cable ducts and outdoors, and may be laid directly in the ground. The -J version carries a green/yellow protective conductor; the -O version has the same construction and dimensions without it. It is available as single-core and 2- to 5-core cables from 1.5 to 630 mm².

German standardDirect burialPower cable

Also known as: underground cable · power cable

Applications

  • Fixed power distribution in buildings, cable ducts and outdoors.
  • Underground installation, direct or in a duct.
  • Projects to German specification (DIN VDE 0276-603).

What to look out for

  • Unarmoured: underground we advise a sand bed with cover tiles or a duct; where damage threatens, choose an armoured type such as VG-YMvKas.
  • J = with green/yellow earth (e.g. 3G1.5), O = without (3×1.5): for circuits with an earth conductor always the J version.
  • Aluminium version: NAYY, more economical in large cross-sections.
  • CPR class Eca. Where the cable is exposed to indoor air in a building, the Bbl requires at least Dca. Choose a type with at least Dca there, such as YMvK Cca or VG-YMvKas.
Construction
Conductor
Plain (bare) copper, solid class 1 or stranded class 2 acc. to IEC 60228 / DIN VDE 0295; circular (RE/RM) or sector-shaped (SM) in the larger multicore sizes.
Insulation
Polyvinyl chloride (PVC), compound type DIV4 acc. to HD 603 S1.
Bedding
Inner PVC covering (bedding) over the laid-up cores.
Sheath
Polyvinyl chloride (PVC), compound type DMV5 acc. to HD 603 S1; black.
Core identification
Acc. to HD 308 S2 / VDE 0293-308; -J with green/yellow protective conductor, -O without.
Electrical & thermal properties
Rated voltage Uo/U
0.6/1 kV (600/1000 V).
Test voltage
4 kV AC.
Standard
DIN VDE 0276-603 (HD 603 S1); IEC 60502-1; conductors acc. to IEC 60228.
Flame-retardant
Acc. to IEC 60332-1-2 / DIN EN 60332-1-2.
Max. conductor temperature
+70 °C in normal operation.
Max. short-circuit temperature
+160 °C (≤ 300 mm²), +140 °C (> 300 mm²), up to 5 s.
Min. bending radius, fixed
12 × outer diameter (multicore); 15 × for single-core.
Which one do I choose?

NYY or NAYY?

NYY

  • copper conductors
  • smaller cross-section

NAYY

  • aluminium conductors
  • larger cross-section

NYY has copper conductors, NAYY aluminium; otherwise the build is the same, with PVC insulation and a black PVC sheath to DIN VDE 0276-603. Aluminium is lighter and more economical, but needs a larger cross-section for the same current and terminals approved for aluminium. For smaller circuits NYY is the simple choice; in large cross-sections NAYY pays off.

View NAYY →

NYY or NYCWY?

NYY

  • green/yellow core among phase cores
  • serves as protective conductor

NYCWY

  • concentric copper wires around cores
  • serves as PEN and screen

NYY-J has a green/yellow core among the phase cores. NYCWY has no green/yellow core but a concentric conductor of copper wires around the cores; it serves as the PEN in a TN-C network and also forms a screen. Choose NYCWY for mains supply and distribution in a TN-C network. For distribution with a green/yellow protective conductor in the cable, choose NYY-J.

View NYCWY →