Skip to content
Underground cables

NAYY

Aluminium PVC power / underground cable, 0.6/1 kV

0.6/1 kV CPR Eca DIN VDE 0276-603 (HD 603)
AL/PVC/PVC On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

NAYY is the aluminium NYY for 0.6/1 kV: lighter and more economical for the large cross-sections of a distribution network, suitable for direct burial. Supplied to order; the lead time is stated in the quote.

NAYY (also (N)AYY) is the aluminium version of NYY: a PVC-insulated power and underground cable for a rated voltage of 0.6/1 kV to DIN VDE 0276-603 (HD 603 S1), with aluminium conductors (solid class 1 / stranded class 2, circular or sector-shaped), PVC core insulation, an inner PVC covering (bedding) and a black PVC outer sheath. It is used for fixed power distribution and mains supply in buildings, cable ducts and outdoors, and may be laid directly in the ground; the light aluminium conductor makes it economical for the larger cross-sections of a distribution network. The -J version carries a green/yellow protective conductor; the -O version has the same construction and dimensions without it. It is available as single-core, 4- and 5-core cables from 16 to 630 mm².

AluminiumDistributionDirect burial

Also known as: aluminium underground cable

Applications

  • Mains supply and distribution where aluminium cuts weight and cost.
  • Fixed power distribution in buildings, ducts and outdoors.
  • Direct burial in the larger cross-sections.

What to look out for

  • Aluminium: bimetallic lugs or terminals approved for aluminium, clean and grease the contact face. Aluminium directly on a copper busbar corrodes.
  • From 16 mm²; for small cross-sections use copper (NYY).
  • Unarmoured: in a sand bed with cover tiles or in conduit; armoured aluminium is VG-YMvKas AL/AL Cca.
  • CPR class Eca. Where the cable is installed permanently in a building and exposed to indoor air, the Bbl requires at least Dca; choose VG-YMvKas Dca ALU there, for example.
Construction
Conductor
Aluminium, solid class 1 or stranded class 2 acc. to IEC 60228 / DIN VDE 0295; circular (RE/RM) or sector-shaped (SE/SM) in the larger multicore sizes.
Insulation
Polyvinyl chloride (PVC), compound type DIV4 acc. to HD 603 S1.
Bedding
Inner PVC covering (bedding) over the laid-up cores.
Sheath
Polyvinyl chloride (PVC), compound type DMV5 acc. to HD 603 S1; black.
Core identification
Acc. to HD 308 S2 / VDE 0293-308; -J with green/yellow protective conductor, -O without.
Electrical & thermal properties
Rated voltage Uo/U
0.6/1 kV (600/1000 V).
Test voltage
4 kV AC.
Standard
DIN VDE 0276-603 (HD 603 S1); IEC 60502-1; conductors acc. to IEC 60228.
Flame-retardant
Acc. to IEC 60332-1-2 / DIN EN 60332-1-2.
Max. conductor temperature
+70 °C in normal operation.
Max. short-circuit temperature
+160 °C (≤ 300 mm²), +140 °C (> 300 mm²), up to 5 s.
Min. bending radius, fixed
12 × outer diameter (multicore); 15 × for single-core.
Which one do I choose?

NAYY or NYY?

NAYY

  • aluminium conductors
  • larger cross-section

NYY

  • copper conductors
  • smaller cross-section

NAYY is the aluminium version of NYY, with the same PVC insulation and black PVC sheath. Aluminium is lighter and more economical, but needs a larger cross-section for the same current and terminals approved for aluminium. For the large cross-sections of a network or main supply choose NAYY, for smaller circuits NYY.

View NYY →

NAYY or NAYCWY?

NAYY

  • green/yellow core as earth
  • among the other cores

NAYCWY

  • concentric conductor, PEN or earth
  • copper, around the cores

Both have aluminium conductors with PVC insulation to VDE 0276-603. On NAYY-J the earth is a green/yellow core among the other cores. NAYCWY instead has a concentric copper conductor around the cores, which serves as PEN or earth. Choose NAYCWY for service connections where that concentric conductor is specified, NAYY for ordinary distribution.

View NAYCWY Eca →