PVC power cable with concentric conductor, 0.6/1 kV

0.6/1 kV CPR Eca DIN VDE 0276-603 (HD 603)
CU/PVC/CWS/PVC On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

NYCWY is the power cable with a concentric copper conductor for 0.6/1 kV: the concentric layer serves as the PEN conductor and screen in TN-C networks. Suitable for direct burial. Supplied to order; the lead time is stated in the quote.

NYCWY is a PVC-insulated power cable for a rated voltage of 0.6/1 kV to DIN VDE 0276-603 (HD 603 S1) with a concentric copper conductor. The plain copper phase conductors (solid class 1 / stranded class 2) have PVC core insulation; over the laid-up cores a concentric conductor of helically applied copper wires in a wave form (the ‘W’) with a copper counter-helix serves as the combined PEN conductor, and a black PVC outer sheath completes the cable. It is used for fixed power distribution and mains supply in TN-C systems where the concentric conductor acts as the protective-and-neutral (PEN) conductor and as an electrical screen, including direct burial in the ground. It is available as 2- to 4-core cables from 10 to 240 mm² (phase).

Concentric (PEN)TN-CDirect burial

Also known as: underground cable

Applications

  • Mains supply and distribution in TN-C systems (PEN via the concentric conductor).
  • Service cables where a screen/PEN is wanted.
  • Direct burial in the ground.

What to look out for

  • The concentric conductor is the PEN; follow the rules for TN-C use.
  • Sizes stated per phase conductor (10 to 240 mm²).
  • CPR class Eca. Where the cable is exposed to indoor air in a building, the Bbl requires at least Dca. Choose a halogen-free type with a concentric conductor there, such as N2XCH, and state the required class with your enquiry.
Construction
Conductor
Plain (bare) copper phase conductor, solid class 1 or stranded class 2 acc. to IEC 60228 / DIN VDE 0295.
Insulation
Polyvinyl chloride (PVC), compound type DIV4 acc. to HD 603 S1.
Concentric conductor
Concentric copper conductor of helically applied bare copper wires in a wave form (‘W’) with an open copper counter-helix tape, over a bedding on the laid-up cores; serves as the PEN conductor (TN-C). Concentric size per phase size (mm²): 10 → 10, 16 → 16, 25 and 35 → 16, 50 → 25, 70 → 35, 95 → 50, 120 and 150 → 70, 185 → 95, 240 → 120.
Sheath
Polyvinyl chloride (PVC), compound type DMV5 acc. to HD 603 S1; black.
Core identification
Acc. to HD 308 S2 / VDE 0293-308; concentric conductor = PEN.
Electrical & thermal properties
Rated voltage Uo/U
0.6/1 kV (600/1000 V).
Test voltage
4 kV AC.
Standard
DIN VDE 0276-603 (HD 603 S1); IEC 60502-1; conductors acc. to IEC 60228.
Flame-retardant
Acc. to IEC 60332-1-2 / DIN EN 60332-1-2.
Max. conductor temperature
+70 °C in normal operation.
Max. short-circuit temperature
+160 °C (≤ 300 mm²), up to 5 s.
Min. bending radius, fixed
12 × outer diameter.
Which one do I choose?

NYCWY or NYY?

NYCWY

  • no green/yellow core
  • concentric conductor: PEN and screen

NYY

  • green/yellow core (NYY-J)
  • green/yellow protective conductor

NYCWY has a concentric conductor of copper wires around the cores. It serves as the PEN and as a screen in a TN-C network, which is why NYCWY has no green/yellow core. NYY-J does have that green/yellow core. For mains supply and distribution in a TN-C network choose NYCWY, for distribution with a green/yellow protective conductor in the cable NYY-J.

View NYY →

NYCWY or NAYCWY?

NYCWY

  • copper phase conductors
  • smaller cross-section

NAYCWY

  • aluminium phase conductors
  • larger cross-section

The difference is in the phase conductors: NYCWY has copper, NAYCWY aluminium. The concentric conductor around the cores is copper on both. NAYCWY is lighter and more economical, but needs a larger cross-section for the same current and terminals approved for aluminium. In large cross-sections NAYCWY pays off; in smaller ones choose NYCWY.

View NAYCWY Eca →