VO-YMvKas Dca

Braid-armoured installation cable 0.6/1 kV, Cu/XLPE/PVC/GSWB/PVC, 90 °C

0.6/1 kV CPR Dca HD 604-S1-4D
CU/XLPE/PVC/GSWB/PVC In stock Lead time: 1–2 working days from stock Send your enquiry
Application

VO-YMvKas Dca is the Dutch underground cable with a galvanised steel wire braid and a tinned copper earth conductor (GSWB): XLPE insulation for 90 °C, flame-retardant PVC sheath, KEMA-KEUR and reaction-to-fire class Dca. In stock in Dordrecht up to 4×6 mm².

VO-YMvKas is the Dutch braid-armoured installation and control cable for 0.6/1 kV fixed power, control and signalling circuits that need mechanical protection and an earth path. The plain copper conductors are insulated with cross-linked polyethylene (XLPE), laid up and covered with a PVC bedding; a braid of galvanised steel wires over a tinned-copper earth strand provides armouring and the earth path, and a PVC outer sheath completes the cable. VO-YMvKas is common in building services, machine rooms and panels where a robust, earthed installation cable is required. The XLPE insulation gives a +90 °C conductor rating. The braided type is made in the smaller cross-sections; for larger power sizes the steel-wire-armoured VG-YMvKas is used instead.

UndergroundBraidedKEMA

Also known as: underground cable

Applications

  • Supply to outbuildings, EV chargers and outdoor installations, directly in the ground without conduit.
  • Industrial sites and farms: cable in the ground that has to withstand spade and stone.
  • Building services, machine rooms and panels where an earthed, armoured installation cable is required.

What to look out for

  • Braid and earth conductor together form the earth path: connect the earth conductor; the braid alone is not enough.
  • Solid class 1 copper: fits terminals directly, no ferrules. Larger cross-sections and class 2: VG-YMvKas.
  • The braid protects against spade and stone, not against an excavator: about 60 cm of cover and warning tape are still needed; we advise a sand bed. Larger power sizes: VG-YMvKas.
  • Single-core YMvKas has a magnetic steel armour, which heats up with alternating current. Single-core is therefore for DC; for AC, choose a multicore cable.
  • From stock, any length cut to size and no minimum. Ordered before 12:00, usually on site within 1–2 working days.
Construction
Conductor
Plain annealed copper, solid class 1 acc. to IEC 60228.
Insulation
Cross-linked polyethylene (XLPE).
Bedding
Polyvinyl chloride (PVC).
Armour
Braid of galvanised steel wires over a tinned-copper earth strand.
Sheath
Polyvinyl chloride (PVC), grey, UV-resistant.
Core identification
Colour-coded acc. to HD 308 S2 without a green/yellow core, or numbered, to order. Earth via the tinned-copper earth strand.
Electrical & thermal properties
Rated voltage Uo/U
0.6/1 kV.
Test voltage
3.5 kV AC.
Standard
HD 604 part 4 section D; conductors acc. to IEC 60228.
Reaction to fire (CPR)
Class Dca-s2,d2,a3 acc. to EN 50575.
Flame-retardant
Acc. to IEC 60332-1-2 and IEC 60332-3-24.
Temperature range
−20 °C to +90 °C (conductor); +250 °C in short circuit.
Min. bending radius, fixed
15 × outer diameter.
Certification
DEKRA K42D-1-1:2017 and DEKRA K42D-1-4-D:2017 (formerly KEMA-KEUR).
Dimensions and technical data

Sizes and weights

Cores × mm²R DC 20 °C (Ω/km)Outer Ø approx. (mm)Weight approx. (kg/km)
1×1.512.110.7161
1×2.57.4111.0180
1×44.6111.5216
1×63.0812.0261
1×101.8313.1356
1×161.1514.0480
1×250.72715.6593
1×350.52416.6698
2×1.512.113.9276
2×2.57.4114.7317
2×44.6115.6388
2×63.0816.6473
2×101.8318.7658
2×161.1520.7896
2×250.72724.41235
2×350.52426.41504
3×1.512.114.4299
3×2.57.4115.2349
3×44.6116.2433
3×63.0817.3535
3×101.8319.5755
3×161.1521.71043
3×250.72725.61462
3×350.52427.81811
4×1.512.115.1331
4×2.57.4116.0391
4×44.6117.1494
4×63.0818.3617
4×101.8320.9878
4×161.1523.31226
4×250.72727.81752
4×350.52430.22193
5×1.512.115.9369
5×2.57.4116.9442
5×44.6118.1559
5×63.0819.5705
5×101.8322.31010
5×161.1525.01419
5×250.72730.02049
5×350.52433.82668

The complete dimension and current-rating tables are in the datasheet.

Current rating

Two-core: single-phase AC or DC (2 loaded conductors)

Cross-section (mm²)C (A)E (A)D1 (A)D2 (A)
1.524262527
2.533363335
445494346
658635358
1080867177
1610711591100
25138149116129
35171185139155

Three- to five-core: three-phase AC (3 loaded conductors)

Cross-section (mm²)C (A)E (A)D1 (A)D2 (A)
1.522232123
2.530322830
440423639
652544449
1071755865
16961007584
2511912796107
35147158115129

Current ratings to NEN 1010, for copper at a conductor temperature of 90 °C and one multi-core cable. Method C: clipped direct on a wall. Method E: in free air or on a perforated cable tray. Method D1: in a duct in the ground. Method D2: direct in the ground. The values apply to one circuit, at 30 °C in air or at 20 °C and a soil thermal resistivity of 2.5 K·m/W in the ground. We recalculate them for your situation.

Which one do I choose?

VO-YMvKas or NYY?

VO-YMvKas Dca

  • galvanised steel wire braid
  • XLPE insulation, 90 °C
  • earth via earth strand

NYY

  • unarmoured
  • PVC insulation, 70 °C
  • green/yellow core in J version

VO-YMvKas has a galvanised steel wire braid and XLPE insulation rated for 90 °C. VO-YMvKas has no green/yellow core: the earth runs through the tinned copper earth strand under the braid. NYY is unarmoured, has PVC insulation rated for 70 °C and, in the J version, a green/yellow core; underground we advise a sand bed with cover tiles or a duct for NYY. Choose NYY mainly for a German specification and VO-YMvKas for a Dutch one.

View NYY →

VO-YMvKas or EXAVB?

VO-YMvKas Dca

  • galvanised steel wire braid
  • earth strand, no green/yellow core

EXAVB

  • steel wire or double steel tape
  • green/yellow core in G version

EXAVB is armoured: steel wire up to and including 10 mm² and a double steel tape from 16 mm². VO-YMvKas has a galvanised steel wire braid and a tinned copper earth strand, with no green/yellow core. On EXAVB the copper protective circuit is not an earth conductor: if you want an earth in the cable, choose the version with a green/yellow core (G). In Belgium choose EXAVB, in the Netherlands VO-YMvKas.

View EXAVB →