VG-YMvKas Dca ALU
Power cable 0.6/1 kV, aluminium conductor, armoured
VG-YMvKas Dca ALU is the aluminium version of the armoured underground cable: aluminium conductors, XLPE insulation, galvanised steel wire armour with earth continuity conductor (GSWA+ECC) and a flame-retardant PVC sheath in reaction-to-fire class Dca, Cca on request. For long routes and large cross-sections, where the weight and copper price of the copper version are major factors.
Armoured power cable with aluminium conductors for 0.6/1 kV, for low-voltage installations to NEN 1010. Suitable for direct burial, also in wet soil but not directly in water, and for installation above ground, for example as a supply cable for main and sub-distribution boards where mechanical protection is needed. The aluminium conductors keep the cable light. Available with three and four cores from 35 to 300 mm².
Also known as: aluminium underground cable
Applications
- Underground distribution over longer distances on business parks and in infrastructure.
- Low-voltage connections of solar parks, charging plazas and transformer stations.
- Underground supply cables to buildings. If the specification calls for Cca, we supply that version on request.
What to look out for
- Aluminium: terminate with bimetallic lugs or terminals approved for aluminium, clean and grease the contact face. Aluminium directly on a copper busbar corrodes.
- The same current needs one to two steps more cross-section than copper: aluminium 4×150 mm² corresponds to copper 4×95 mm².
- For the same current, a larger outer diameter and bending radius than the copper VG-YMvKas: check entries, glands and bends in the route accordingly.
- Connect armour and earth continuity conductor together as the earth path, at both ends.
- Conductor
- Stranded aluminium, class 2 acc. to IEC 60228, sector-shaped.
- Insulation
- Cross-linked polyethylene (XLPE).
- Inner sheath
- Polyvinyl chloride (PVC).
- Armour
- Galvanised round steel wires with bare round copper wires as earth continuity conductor (ECC), held by an open counter-helix of galvanised steel tape.
- Outer sheath
- Polyvinyl chloride (PVC), flame-retardant, UV-resistant, grey.
- Core identification
- Colour-coded acc. to HD 308. Standard version without green/yellow core: earth via the earth continuity conductor in the armour. Version with green/yellow core on request.
- Rated voltage Uo/U
- 0.6/1 kV.
- Test voltage
- 4 kV AC.
- Max. conductor temperature
- +90 °C; +250 °C in short circuit.
- Operating temperature
- 0 °C to +80 °C.
- Min. installation temperature
- 0 °C.
- Min. bending radius
- 16 × outer diameter.
- Standards
- HD 604 S1 and IEC 60502-1; conductors acc. to IEC 60228; core colours acc. to HD 308.
- Flame-retardant
- Acc. to IEC 60332-1-2.
- Reaction to fire (CPR)
- Dca-s2,d2,a3 acc. to EN 50575; Cca on request.
Sizes and weights
| Cores × mm² | R DC 20 °C (Ω/km) | Outer Ø approx. (mm) | Weight approx. (kg/km) |
|---|---|---|---|
| 3×35/16 | 0.868 | 24.6 | 1109 |
| 3×50/16 | 0.641 | 27.0 | 1344 |
| 3×70/20 | 0.443 | 31.7 | 1869 |
| 3×95/30 | 0.320 | 34.9 | 2272 |
| 3×95/35 | 0.320 | 35.7 | 2466 |
| 3×120/35 | 0.253 | 38.7 | 2944 |
| 3×150/45 | 0.206 | 43.0 | 3470 |
| 3×185/60 | 0.164 | 47.9 | 4518 |
| 3×240/75 | 0.125 | 53.3 | 5356 |
| 3×300/95 | 0.100 | 59.2 | 7041 |
| 4×35/16 | 0.868 | 27.2 | 1289 |
| 4×50/16 | 0.641 | 30.3 | 1593 |
| 4×70/20 | 0.443 | 35.4 | 2243 |
| 4×95/30 | 0.320 | 39.0 | 2718 |
| 4×120/35 | 0.253 | 44.1 | 3499 |
| 4×150/45 | 0.206 | 48.0 | 4150 |
| 4×185/60 | 0.164 | 53.8 | 5290 |
| 4×240/75 | 0.125 | 59.9 | 6432 |
| 4×300/95 | 0.100 | 66.1 | 8244 |
The figure after the slash is the cross-section of the earth screen in mm². The resistance is the maximum for class 2 aluminium to IEC 60228.
The complete dimension and current-rating tables are in the datasheet.
Three- and four-core: three-phase AC (3 loaded conductors)
| Cross-section (mm²) | C (A) | E (A) | D1 (A) | D2 (A) |
|---|---|---|---|---|
| 35 | 112 | 120 | 90 | 98 |
| 50 | 136 | 146 | 106 | 117 |
| 70 | 174 | 187 | 130 | 144 |
| 95 | 211 | 227 | 154 | 172 |
| 120 | 245 | 263 | 174 | 197 |
| 150 | 283 | 304 | 197 | 220 |
| 185 | 323 | 347 | 220 | 250 |
| 240 | 382 | 409 | 253 | 290 |
| 300 | 440 | 471 | 286 | 326 |
Current ratings to NEN 1010, for aluminium at a conductor temperature of 90 °C and one multi-core cable. Method C: clipped direct on a wall. Method E: in free air or on a perforated cable tray. Method D1: in a duct in the ground. Method D2: direct in the ground. The values apply to one circuit, at 30 °C in air or at 20 °C and a soil thermal resistivity of 2.5 K·m/W in the ground. We recalculate them for your situation.
VG-YMvKas Dca ALU or AL/AL?
VG-YMvKas Dca ALU
- galvanised steel wire
- copper wire earth conductor (ECC)
VG-YMvKas AL/AL
- round aluminium wires
- earth via the armour
Both have aluminium conductors, XLPE insulation and no green/yellow core. The difference is the armour, and with it the earth. VG-YMvKas Dca ALU has galvanised steel wire with an earth continuity conductor of copper wires (ECC); on VG-YMvKas AL/AL the armour of round aluminium wires carries the earth itself. If you want to connect the earth to copper, choose the Dca ALU; with AL/AL the glands must also be suitable for aluminium.
View VG-YMvKas AL/AL Cca →VG-YMvKas Dca ALU or the copper VG-YMvKas?
VG-YMvKas Dca ALU
- aluminium conductors
- terminals approved for aluminium
VG-YMvKas Dca
- copper conductors
- connects directly to copper terminals
Armour with earth continuity conductor (GSWA+ECC), XLPE insulation, PVC sheath and CPR class Dca-s2,d2,a3 are the same; the main difference is the conductor. Aluminium is lighter and more economical, but needs a larger cross-section for the same current and bimetallic lugs or terminals approved for aluminium. Aluminium pays off mainly on long routes and in large cross-sections; copper connects directly to copper terminals.
View VG-YMvKas Dca →