VG-YMvKas Dca ALU

Power cable 0.6/1 kV, aluminium conductor, armoured

0.6/1 kV CPR Dca HD 604 S1 / IEC 60502-1
AL/XLPE/PVC/GSWA+ECC/PVC On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

VG-YMvKas Dca ALU is the aluminium version of the armoured underground cable: aluminium conductors, XLPE insulation, galvanised steel wire armour with earth continuity conductor (GSWA+ECC) and a flame-retardant PVC sheath in reaction-to-fire class Dca, Cca on request. For long routes and large cross-sections, where the weight and copper price of the copper version are major factors.

Armoured power cable with aluminium conductors for 0.6/1 kV, for low-voltage installations to NEN 1010. Suitable for direct burial, also in wet soil but not directly in water, and for installation above ground, for example as a supply cable for main and sub-distribution boards where mechanical protection is needed. The aluminium conductors keep the cable light. Available with three and four cores from 35 to 300 mm².

AluminiumUndergroundArmoured

Also known as: aluminium underground cable

Applications

  • Underground distribution over longer distances on business parks and in infrastructure.
  • Low-voltage connections of solar parks, charging plazas and transformer stations.
  • Underground supply cables to buildings. If the specification calls for Cca, we supply that version on request.

What to look out for

  • Aluminium: terminate with bimetallic lugs or terminals approved for aluminium, clean and grease the contact face. Aluminium directly on a copper busbar corrodes.
  • The same current needs one to two steps more cross-section than copper: aluminium 4×150 mm² corresponds to copper 4×95 mm².
  • For the same current, a larger outer diameter and bending radius than the copper VG-YMvKas: check entries, glands and bends in the route accordingly.
  • Connect armour and earth continuity conductor together as the earth path, at both ends.
Construction
Conductor
Stranded aluminium, class 2 acc. to IEC 60228, sector-shaped.
Insulation
Cross-linked polyethylene (XLPE).
Inner sheath
Polyvinyl chloride (PVC).
Armour
Galvanised round steel wires with bare round copper wires as earth continuity conductor (ECC), held by an open counter-helix of galvanised steel tape.
Outer sheath
Polyvinyl chloride (PVC), flame-retardant, UV-resistant, grey.
Core identification
Colour-coded acc. to HD 308. Standard version without green/yellow core: earth via the earth continuity conductor in the armour. Version with green/yellow core on request.
Electrical & thermal properties
Rated voltage Uo/U
0.6/1 kV.
Test voltage
4 kV AC.
Max. conductor temperature
+90 °C; +250 °C in short circuit.
Operating temperature
0 °C to +80 °C.
Min. installation temperature
0 °C.
Min. bending radius
16 × outer diameter.
Standards
HD 604 S1 and IEC 60502-1; conductors acc. to IEC 60228; core colours acc. to HD 308.
Flame-retardant
Acc. to IEC 60332-1-2.
Reaction to fire (CPR)
Dca-s2,d2,a3 acc. to EN 50575; Cca on request.
Dimensions and technical data

Sizes and weights

Cores × mm²R DC 20 °C (Ω/km)Outer Ø approx. (mm)Weight approx. (kg/km)
3×35/160.86824.61109
3×50/160.64127.01344
3×70/200.44331.71869
3×95/300.32034.92272
3×95/350.32035.72466
3×120/350.25338.72944
3×150/450.20643.03470
3×185/600.16447.94518
3×240/750.12553.35356
3×300/950.10059.27041
4×35/160.86827.21289
4×50/160.64130.31593
4×70/200.44335.42243
4×95/300.32039.02718
4×120/350.25344.13499
4×150/450.20648.04150
4×185/600.16453.85290
4×240/750.12559.96432
4×300/950.10066.18244

The figure after the slash is the cross-section of the earth screen in mm². The resistance is the maximum for class 2 aluminium to IEC 60228.

The complete dimension and current-rating tables are in the datasheet.

Current rating

Three- and four-core: three-phase AC (3 loaded conductors)

Cross-section (mm²)C (A)E (A)D1 (A)D2 (A)
351121209098
50136146106117
70174187130144
95211227154172
120245263174197
150283304197220
185323347220250
240382409253290
300440471286326

Current ratings to NEN 1010, for aluminium at a conductor temperature of 90 °C and one multi-core cable. Method C: clipped direct on a wall. Method E: in free air or on a perforated cable tray. Method D1: in a duct in the ground. Method D2: direct in the ground. The values apply to one circuit, at 30 °C in air or at 20 °C and a soil thermal resistivity of 2.5 K·m/W in the ground. We recalculate them for your situation.

Which one do I choose?

VG-YMvKas Dca ALU or AL/AL?

VG-YMvKas Dca ALU

  • galvanised steel wire
  • copper wire earth conductor (ECC)

VG-YMvKas AL/AL

  • round aluminium wires
  • earth via the armour

Both have aluminium conductors, XLPE insulation and no green/yellow core. The difference is the armour, and with it the earth. VG-YMvKas Dca ALU has galvanised steel wire with an earth continuity conductor of copper wires (ECC); on VG-YMvKas AL/AL the armour of round aluminium wires carries the earth itself. If you want to connect the earth to copper, choose the Dca ALU; with AL/AL the glands must also be suitable for aluminium.

View VG-YMvKas AL/AL Cca →

VG-YMvKas Dca ALU or the copper VG-YMvKas?

VG-YMvKas Dca ALU

  • aluminium conductors
  • terminals approved for aluminium

VG-YMvKas Dca

  • copper conductors
  • connects directly to copper terminals

Armour with earth continuity conductor (GSWA+ECC), XLPE insulation, PVC sheath and CPR class Dca-s2,d2,a3 are the same; the main difference is the conductor. Aluminium is lighter and more economical, but needs a larger cross-section for the same current and bimetallic lugs or terminals approved for aluminium. Aluminium pays off mainly on long routes and in large cross-sections; copper connects directly to copper terminals.

View VG-YMvKas Dca →