Power cable 0.6/1 kV, aluminium conductor, concentric copper conductor

0.6/1 kV CPR Eca DIN VDE 0276-603
AL/PVC/CU(conc.)/PVC On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

NAYCWY Eca is the German service cable to VDE 0276-603: aluminium conductors with PVC insulation, a concentric copper conductor as PEN or earth, and a black PVC sheath. For fixed installation indoors, outdoors, underground, in water and in concrete. The concentric conductor makes a separate earth core unnecessary.

NAYCWY is a 0.6/1 kV power cable to DIN VDE 0276-603 (HD 603 S1) with aluminium conductors, PVC insulation and a concentric copper conductor under a black PVC outer sheath. It is used for power distribution in power stations, industrial installations, switchgear and local mains, for fixed installation indoors, in cable ducts, outdoors, in the ground, in water and in concrete, where protection against contact voltage in the event of mechanical damage or electrical screening is required. The concentric conductor serves as the protective conductor (PE) or as the combined protective and neutral conductor (PEN); its wave form allows branch joints without cutting it. Available with 2, 3 and 4 cores from 16 to 240 mm², with round or sector-shaped conductors.

AluminiumConcentricIn water & concrete

Also known as: aluminium underground cable

Applications

  • Service connections and distribution mains in the ground, to VDE 0276-603.
  • Supply to buildings and installations where the concentric conductor serves as PEN.
  • Fixed installation in concrete and in water, for example pumping stations and sumps.

What to look out for

  • Aluminium conductors, copper concentric conductor: use bimetallic or aluminium-rated terminals for the aluminium cores and grease the contact face.
  • CPR class Eca. Where the cable is exposed to indoor air in a building, the Bbl requires at least Dca.
Construction
Conductor
Aluminium, solid (class 1) or stranded (class 2) acc. to IEC 60228, round or sector-shaped (see the shape column).
Insulation
Polyvinyl chloride (PVC), type DIV 4.
Inner covering
Over the laid-up cores, extruded elastomer or plastomer compound or tape, depending on the manufacturer.
Concentric conductor
Bare copper wires applied in wave form, with a copper tape counter helix.
Outer sheath
Polyvinyl chloride (PVC), type DMV 5, black, UV-resistant.
Core identification
Acc. to HD 308. 2-core: blue, brown. 3-core: brown, black, grey. 4-core: blue, brown, black, grey. There is no green/yellow core: the protective earth runs through the concentric copper conductor.
Electrical & thermal properties
Rated voltage Uo/U
0.6/1 kV.
Max. operating voltage, three-phase systems
1.2 kV.
Rated voltage DC (core-earth/core-core)
1.8/1.8 kV.
Test voltage
4 kV AC.
Max. conductor temperature
70 °C in operation; 160 °C in short circuit (max. 5 s).
Operating temperature, fixed
−35 °C to +70 °C.
Min. installation temperature
−5 °C.
Min. bending radius
12 × outer diameter.
Earthing
Through the concentric copper conductor (PE or PEN).
CPR classification
Eca acc. to EN 50575.
Standard
DIN VDE 0276-603 (HD 603 S1, part 3G); IEC 60502-1. Conductors acc. to IEC 60228.
Flame-retardant
IEC 60332-1-2 / EN 60332-1-2.
Dimensions and technical data

Sizes and weights

Cores × mm²ShapeInsulation (mm)Sheath (mm)Outer Ø approx. (mm)Weight approx. (kg/km)R DC 20 °C (Ω/km)Ik 1 s (kA)
2×16/16RE1.01.8205841.911.22
3×16/16RM1.01.8216441.911.22
3×25/16RM1.21.8268871.201.90
3×50/25SM1.41.9291,2480.6413.80
3×50/50SE1.41.9281,3150.6413.80
3×70/70SE1.42.0331,7720.4435.32
3×95/50SM1.62.2372,0990.3207.22
3×95/95SE1.62.2372,3260.3207.22
3×120/70SM1.62.3412,5650.2539.12
3×120/120SE1.62.3392,7830.2539.12
3×150/70SM1.82.4453,0830.20611.40
3×150/150SM1.82.4453,5130.20611.40
3×150/150SE1.82.4433,3770.20611.40
3×185/95SM2.02.6503,7600.16414.06
3×185/185SM2.02.6504,3240.16414.06
3×185/185SE2.02.6474,1550.16414.06
3×240/120SM2.22.9574,7810.12518.24
3×240/240SE2.22.8565,6040.12518.24
4×16/16RE1.01.8237391.911.22
4×25/16RM1.21.8281,0521.201.90
4×25/16RE1.21.8271,0061.201.90
4×35/16RE1.21.8291,2270.8682.66
4×50/25SM1.42.0311,5510.6413.80
4×50/25SE1.42.0311,4740.6413.80
4×70/35SM1.42.1351,9820.4435.32
4×70/35SE1.42.1341,8710.4435.32
4×95/50SM1.62.3402,5880.3207.22
4×95/50SE1.62.3392,4730.3207.22
4×120/70SM1.62.4453,2370.2539.12
4×120/70SE1.62.4433,1170.2539.12
4×150/70SM1.82.6503,8710.20611.40
4×150/70SE1.82.6473,6950.20611.40
4×185/95SM2.02.8554,7540.16414.06
4×185/95SE2.02.8534,5390.16414.06
4×240/120SM2.23.0626,1000.12518.24
4×240/120SE2.23.0585,7860.12518.24

Size given as phase conductor / concentric copper conductor. Shape: RE = round, solid (class 1); RM = round, stranded (class 2); SE = sector-shaped, solid; SM = sector-shaped, stranded. Short-circuit current: aluminium conductor, 1 s, from 70 to 160 °C. We confirm the weights of the two 3×240 constructions on request. Outer diameter and weight differ per delivery: choose glands with margin.

The complete dimension and current-rating tables are in the datasheet.

Current rating

Two-core: single-phase AC or DC (2 loaded conductors)

Cross-section (mm²)C (A)E (A)D1 (A)D2 (A)
1666736163

Three- and four-core: three-phase AC (3 loaded conductors)

Cross-section (mm²)C (A)E (A)D1 (A)D2 (A)
1659615053
2573786469
3590967783
501101179199
70140150112122
95170183132148
120197212150169
150227245169189
185259280190214
240305330218250

Current ratings to NEN 1010, for aluminium at a conductor temperature of 70 °C and one multi-core cable; the concentric conductor does not count as a loaded conductor. Method C: clipped direct on a wall. Method E: in free air or on a perforated cable tray. Method D1: in a duct in the ground. Method D2: direct in the ground. The values apply to one circuit, at 30 °C in air or at 20 °C and a soil thermal resistivity of 2.5 K·m/W in the ground. We recalculate them for your situation.

Which one do I choose?

NAYCWY or NYCWY?

NAYCWY Eca

  • aluminium phase conductors
  • larger cross-section

NYCWY

  • copper phase conductors
  • smaller cross-section

NAYCWY has aluminium phase conductors, NYCWY copper ones; the concentric conductor around the cores is copper on both. Aluminium is lighter and more economical, but needs a larger cross-section for the same current and bimetallic or aluminium-rated terminals. Choose NAYCWY in the larger cross-sections, NYCWY in the smaller ones.

View NYCWY →

NAYCWY or NAYY?

NAYCWY Eca

  • concentric conductor, PEN or earth
  • copper, around the cores

NAYY

  • green/yellow core as earth
  • among the other cores

Both have aluminium conductors with PVC insulation to VDE 0276-603. NAYCWY has a concentric copper conductor around the cores, which serves as PEN or earth. NAYY-J has a green/yellow core among the other cores for that purpose. If the service connection calls for a concentric conductor, choose NAYCWY; for ordinary distribution NAYY will do.

View NAYY →