Skip to content
Industrial & rubber

Motor cable 2YSLCY-J

Screened motor connection cable for frequency converters (VFD), 0.6/1 kV

0.6/1 kV CPR Eca EN 50525 / EMC EN 55011
CU/PE/TCWB/PVC On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

2YSLCY-J is the EMC motor cable for variable-frequency drives: low-capacitance PE insulation, symmetrical build and a double screen that carries the HF return currents cleanly. Supplied to order; the lead time is stated in the quote.

2YSLCY-J is a screened power cable for the connection of frequency-inverter-driven (variable-frequency-drive, VFD) motors, rated 0.6/1 kV. The finely stranded bare copper conductors are insulated with polyethylene (PE, the low-capacitance '2Y' compound that keeps charging currents and reflections low on inverter outputs) and laid up symmetrically as a four-core power group with a green/yellow protective conductor (J). An EMC screen of a plastic-coated aluminium foil plus a braided screen of tinned copper wires (approx. 85% coverage) surrounds the cores, and a PVC outer sheath protects the cable. The double screen carries the high-frequency return currents of the inverter and, when bonded to earth at both ends over a large contact area, gives interference-free operation of the drive system.

VFD/driveScreenedEMC

Also known as: motor cable · VFD cable · inverter cable · drive cable

Applications

  • Connection of VFD-driven motors in machines and installations.
  • Circuits where EMC and interference-free drive operation are critical.

What to look out for

  • Earth the screen at both ends over a large area (360 degrees) for EMC.
  • On long motor cables the drive manufacturer sets the maximum cable length, not the current rating; give length and switching frequency with the enquiry.
  • CPR class Eca. Where the cable is installed permanently in a building and exposed to indoor air, the Bbl requires at least Dca. The wiring inside a control panel or machine is not covered by that requirement, but the cables running to it are.
Construction
Conductor
Finely stranded bare annealed copper, class 5 to IEC/EN 60228 (VDE 0295).
Insulation
Polyethylene (PE); low-capacitance '2Y' compound for frequency-converter duty.
Screen
EMC double screen: plastic-coated aluminium foil plus a braided screen of tinned copper wires (TCWB), approx. 85% coverage.
Sheath
PVC compound (transparent or black). PUR and halogen-free (LSZH) sheath variants are available.
Core identification
Brown / black / grey power cores plus a green/yellow protective conductor (J) acc. to VDE 0293-334.
Electrical & thermal properties
Rated voltage Uo/U
0.6/1 kV.
Test voltage
4 kV.
Standard
Construction acc. to DIN VDE 0250 / EN 50525 basis; EMC acc. to VDE 0875-11 / EN 55011.
Flame-retardant
IEC/EN 60332-1-2 (VDE 0482-332-1-2).
Conductor standard
IEC/EN 60228 class 5 (VDE 0295).
Max. conductor temperature
+70 °C (short-circuit +160 °C).
Permitted outer cable temperature, fixed
−40 °C to +70 °C.
Permitted outer cable temperature, flexing
−5 °C to +70 °C.
Min. bending radius, fixed
4 × outer diameter.
Min. bending radius, flexing
15 × outer diameter (10–20 × by size).
EMC screen
Symmetrical 4-core build with double screen; bond the screen to earth at both ends over a large contact area for interference-free VFD operation.
Which one do I choose?

2YSLCY-J or YMvK on the output of a frequency converter?

Motor cable 2YSLCY-J

  • double screen, foil and braid

YMvK

  • no screen

A frequency converter puts steep switching edges on the motor cable. 2YSLCY-J is built for that: low-capacitance PE insulation, a symmetrical construction and a double screen of foil and copper braid that carries the high-frequency return currents away. YMvK has no screen, so the high-frequency interference radiates into the surroundings. Between drive and motor choose 2YSLCY-J; for the supply to the drive an installation cable such as YMvK is enough.

View YMvK Cca →

2YSLCY-J or YSLYCY?

Motor cable 2YSLCY-J

  • power cable
  • 0.6/1 kV
  • PE insulation

YSLYCY

  • control cable
  • 300/500 V
  • PVC insulation

YSLYCY is a screened control cable for 300/500 V with PVC insulation and numbered cores. 2YSLCY-J is a 0.6/1 kV power cable with a double screen and PE insulation, which keeps capacitance, and so the charging currents at the inverter output, low. For the motor supply from the drive, choose 2YSLCY-J; YSLYCY is for the control and signal circuits running alongside that motor cable.

View YSLYCY-JZ →