EXGB
Belgian NBN copper halogen-free outdoor cable, Cca, 0.6/1 kV
EXGB is the halogen-free outdoor cable for 0.6/1 kV: LSZH fire safety in a black sheath for outdoor use and CPR class Cca-s1,d2,a1. For outdoor distribution and ground ducts. Supplied to order; the lead time is stated in the quote.
EXGB is the copper, halogen-free, outdoor version of the Belgian XGB cable to NBN HD 603-5A for 0.6/1 kV power and distribution circuits. The copper conductors are insulated with cross-linked polyethylene (XLPE), assembled with a halogen-free (LSZH) bedding and protected by a black, halogen-free, low-smoke (LSZH) outer sheath. EXGB combines the fire safety of a halogen-free cable (no corrosive halogen gases and very little smoke) with a black sheath for outdoor use. It is used for service connections, yard and site distribution and feeders, outdoors and in ground ducts. Its reaction-to-fire performance is CPR class Cca-s1,d2,a1. The aluminium equivalent is EAXeGB; the standard indoor halogen-free cable is XGB (NBN HD 604-5-L).
Also known as: halogen-free outdoor cable
Applications
- Halogen-free outdoor distribution: service connections, yard and site feeders.
- Outdoors and in ground ducts, where a low-smoke cable is required.
- Belgian projects that call for a halogen-free outdoor cable.
What to look out for
- Halogen-free and low smoke, but flame-retardant, not fire-resistant.
- Indoor halogen-free: XGB. Aluminium: EAXeGB.
- Conductor
- Plain annealed copper, solid class 1 (RE) or stranded class 2 (RM/SM) acc. to IEC 60228.
- Insulation
- Cross-linked polyethylene (XLPE), 90 °C rated.
- Core identification
- Coloured cores acc. to HD 308 S2, with or without green/yellow earth.
- Bedding
- Halogen-free (LSZH) extruded common core covering.
- Outer sheath
- Halogen-free, low-smoke (LSZH) compound, black; for outdoor and in-duct use.
- Rated voltage Uo/U
- 0.6/1 kV.
- Test voltage
- 3.5 kV AC.
- Standard
- NBN HD 603-5A (2023) / Synergrid C1/107; conductor acc. to IEC 60228. Reaction to fire (CPR) Class Cca-s1,d2,a1 acc. to EN 50575 / EN 50399.
- Halogen-free / low smoke
- Halogen-free acc. to IEC/EN 60754-1/-2; low smoke density acc. to IEC/EN 61034-1/-2; flame-retardant acc. to IEC 60332-1-2.
- Max. conductor temperature
- +90 °C (short circuit +250 °C, max. 5 s).
- Permitted ambient temperature, fixed
- −25 °C to +60 °C; min. laying temperature −5 °C.
- Min. bending radius, fixed
- 12 × outer diameter.
EXGB or EXVB?
EXGB
- LSZH bedding and sheath
- CPR class Cca-s1,d2,a1
EXVB
- PVC bedding and sheath
- CPR class Eca
EXGB and EXVB are both Belgian outdoor cables with XLPE cores and a black sheath. EXGB has a bedding and sheath of halogen-free, low-smoke material (LSZH) and CPR class Cca-s1,d2,a1. EXVB has PVC and class Eca. Choose EXGB where halogen-free and low smoke matter or a higher fire class is required; otherwise EXVB will do.
View EXVB →EXGB or EAXeGB?
EXGB
- copper conductors
EAXeGB
- aluminium conductors
Both are halogen-free Belgian cables for 0.6/1 kV with XLPE insulation and CPR class Cca-s1,d2,a1. EXGB has copper conductors. EAXeGB has aluminium conductors and a water blocking tape that makes the cable longitudinally watertight. Aluminium is lighter and more economical, but needs bimetallic lugs or terminals approved for aluminium; for heavy supplies choose EAXeGB, for smaller cross-sections EXGB.
View EAXeGB →