JE-H(St)H Bd FE180

Halogen-free fire-resistant screened fire-alarm cable, 225/400 V, FE180 E30–E90

225/400 V CPR Cca DIN VDE 0815 / IEC 60331
CU/MGT/XLPE/CAM/LSZH On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

JE-H(St)H Bd FE180 is the fire-resistant fire-alarm cable: screened pairs with a mica tape for FE180 circuit integrity, halogen-free, for fire-alarm and evacuation systems. Supplied to order; the lead time is stated in the quote.

JE-H(St)H Bd FE180 is a halogen-free, fire-resistant, collectively screened cable for fire-detection and alarm systems, signalling and telecommunication circuits that must keep operating during a fire. Solid bare-copper pairs (0.8 mm) are wrapped with a mica-glass fire-barrier tape and halogen-free cross-linked insulation to maintain circuit integrity to FE180 (IEC 60331); the assembled, bundle-stranded ('Bd') elements are enclosed by a collective (overall) screen (St) of aluminium/polyester foil in contact with a tinned copper drain wire, which protects the signal pairs against electromagnetic interference. The complete cable reaches system integrity classes E30 to E90 to DIN 4102-12 depending on the mounting. The low smoke zero halogen (LSZH) sheath is orange and, when burning, emits low smoke and no corrosive halogen gases. The cable is not intended for power distribution.

Circuit integrityFire alarmScreened

Also known as: fire-resistant fire-alarm cable

Applications

  • Fire-alarm, evacuation and voice-alarm systems.
  • Control and signalling of safety systems with circuit integrity.

What to look out for

  • 2×2×0.8 is the standard size for fire-alarm and evacuation systems; for loudspeaker circuits with more current choose NHXH FE180 1.5 mm².
  • The E class follows from the approved mounting system.
Construction
Conductor
Solid bare (plain) annealed copper, 0.8 mm diameter (~0.5 mm²), class 1 acc. to IEC 60228 / VDE 0815.
Fire barrier
Mica-glass fire-resistant tape over each conductor, under the insulation; the barrier that maintains insulation integrity under flame (FE180).
Insulation
Halogen-free cross-linked compound (HX).
Screen
(St) Collective (overall) screen of aluminium/polyester (Al/PET) foil in contact with a tinned copper drain wire (CAM).
Sheath
Halogen-free, flame-retardant, low-smoke (LSZH) compound; orange (red also available).
Core identification
Pairs colour-coded and numbered; the elements are bundle-stranded ('Bd').
Electrical & thermal properties
Operating voltage
225 V peak operating voltage (225/400 V; not for power distribution).
Test voltage
800 V.
Fire resistance (circuit integrity)
FE180 acc. to IEC 60331 (insulation integrity maintained 180 min under flame).
System integrity
E30 to E90 acc. to DIN 4102-12 (30 to 90 min functional integrity of the installed circuit, depending on the mounting system).
Standard
DIN VDE 0815 (installation/telecom cables); conductors acc. to IEC 60228; fire tests IEC 60331 and DIN 4102-12.
Flame-retardant
Acc. to IEC 60332-3-24 category C (bunched).
Halogen-free / low smoke
Halogen-free acc. to IEC 60754-1/-2 (corrosive gas); low smoke acc. to IEC 61034-1/-2.
Reaction to fire (CPR)
Cca-s1,d1,a1 (EN 50575); B2ca-s1a,d1,a1 on request.
Loop resistance
Max. 73.2 Ω/km (per conductor ~36.6 Ω/km at 20 °C).
Mutual capacitance
max. 120 nF/km at 800 Hz.
Insulation resistance
min. 100 MΩ × km.
Max. conductor temperature
+70 °C in normal operation.
Min. bending radius, fixed
6 × outer diameter.
Which one do I choose?

JE-H(St)H Bd FE180 or JE-Y(St)Y?

JE-H(St)H Bd FE180

  • halogen-free
  • mica tape around each conductor
  • FE180 to IEC 60331

JE-Y(St)Y

  • PVC insulation and sheath
  • no mica tape
  • no circuit integrity

JE-Y(St)Y has PVC insulation and a PVC sheath without mica tape: flame-retardant, but without circuit integrity. JE-H(St)H Bd FE180 is halogen-free and has a mica tape around each conductor, so the insulation stays intact for 180 minutes in the IEC 60331 fire test (FE180). Choose JE-H(St)H Bd FE180 for fire-alarm and evacuation circuits that must keep working during a fire, and JE-Y(St)Y for measuring and control circuits without that requirement.

View JE-Y(St)Y →

JE-H(St)H Bd FE180 or NHXH FE180?

JE-H(St)H Bd FE180

  • signal cable with pairs
  • screened

NHXH FE180

  • 0.6/1 kV power cable
  • no screen

Both have a mica tape under the insulation and achieve FE180, with E30 to E90 depending on the mounting system. JE-H(St)H Bd FE180 is a screened signal cable with 0.8 mm pairs and is not intended for power. NHXH FE180 is a 0.6/1 kV power cable, without a screen. Choose JE-H(St)H Bd FE180 for detector loops and buses, and NHXH FE180 for the supply of lifts, smoke extraction and fire pumps.

View NHXH FE180 →