RZ1-K (AS)

Halogen-free flexible power cable, class 5 copper, XLPE, 0.6/1 kV

0.6/1 kV CPR Cca UNE 21123-4
CU/XLPE/LSZH On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

RZ1-K (AS) is the halogen-free counterpart of RV-K: the same flexible 0.6/1 kV cable with fine-stranded class 5 copper and XLPE, but with a green halogen-free sheath and class Cca-s1b,d1,a1. Supplied to order; the lead time is stated in the quote.

RZ1-K (AS) is a halogen-free, flexible 0.6/1 kV power cable to UNE 21123-4 for power transmission and distribution in fixed indoor and outdoor installations and for industrial use. It can be installed on open supports, in conduit or buried. Fine-stranded class 5 copper with XLPE insulation for 90 °C, under a green halogen-free sheath. Low smoke and limited fire propagation: class Cca-s1b,d1,a1.

Halogen-freeFlexibleCca

Applications

  • Fixed supply to distribution boards, machines and installations in buildings where the Bbl requires Dca or Cca.
  • Awkward cable routes indoors and outdoors, on cable trays and in conduit.
  • In the ground or in a buried duct, where the specification asks for halogen-free.

What to look out for

  • Class 5 conductor: use ferrules or crimp lugs, never bare under a screw terminal.
  • Not in an extra protected escape route: there the Bbl requires B2ca with smoke class s1.
  • Install from 0 °C, measured on the cable itself. Warm a cold cable first, for example in a heated room.
Construction
Conductor
Plain copper, flexible, class 5 acc. to EN 60228.
Insulation
Cross-linked polyethylene (XLPE), type DIX-3.
Core identification
1×: translucent. Up to 5 cores: blue, brown, black, grey, green/yellow. 6 cores and more: black, numbered, with green/yellow.
Assembly
Concentric stranding.
Bedding
Halogen-free thermoplastic compound (LSZH), optional; natural.
Outer sheath
Halogen-free compound, type DMZ-E; green.
Electrical & thermal properties
Rated voltage Uo/U
0.6/1 kV AC; 0.9/1.5 kV DC.
Max. voltage Um
1.2 kV AC; 1.8 kV DC max. (core to core, without earthing).
Test voltage
3.5 kV AC.
Max. conductor temperature
+90 °C; +250 °C in short circuit (max. 5 s, acc. to IEC 60724).
Min. service temperature
−40 °C (fixed and protected installations).
Min. installation temperature
0 °C, measured on the cable itself, not the surroundings. A colder cable must first be warmed, for example in a heated room.
Reaction to fire (CPR)
Cca-s1b,d1,a1 acc. to EN 50575.
Flame-retardant
Acc. to EN 60332-1-2.
Fire propagation
Acc. to EN 50399.
Low smoke
Light transmittance above 60% acc. to EN 61034-2.
Halogen-free
HCl below 0.5% acc. to EN 60754-1.
Corrosivity
pH 4.3 or higher and conductivity 100 µS/cm or lower acc. to EN 60754-2.
Min. bending radius
During installation: 4 × D for D below 25 mm; 5 × D from 25 to 50 mm; 6 × D above 50 mm (D = outer diameter).
Water
AD7 (intermittent immersion) acc. to IEC 60364-5-51; IPX7 acc. to EN 60529.
Hydrocarbon resistance
Acc. to ICEA S-73-532.
UV resistance
Acc. to UNE 21123-4.
Installation
Fixed, indoor and outdoor; on open supports, in conduit or buried.
Sizes
1×1.5 to 1×300 mm²; two-core up to 2×70, three-core up to 3×95, four-core up to 4×70, five-core up to 5G50; 7 to 14 cores in 1.5, 2.5 and 4 mm²; other constructions on request.
Standard
UNE 21123-4.
Dimensions and technical data

Sizes, weights and current rating

Cores × mm²Outer Ø approx. (mm)Weight approx. (kg/km)R DC 20 °C (Ω/km)Air 40 °C (A)Ground 25 °C (A)Voltage drop (V/A·km)
1×1.57.47013.3212129.374
1×2.57.8807.98302717.624
1×48.51054.95403510.933
1×69.11303.3052447.288
1×1010.01751.9172584.218
1×1611.32451.2197752.673
1×2512.93450.780122961.723
1×3514.34550.5541531171.223
1×5015.96050.3861881380.852
1×7018.58600.2722431700.601
1×9520.210750.2062982020.456
1×12022.413600.1613502300.355
1×15024.416550.1294012600.284
1×18526.820000.1064602910.234
1×24030.926250.08015453360.177
1×30034.033050.06416303800.142
2×1.58.8-13.3232433.918
2×2.59.6-7.98323220.35
2×411.92204.95444212.624
2×613.02803.3057538.416
2×1015.24001.9178704.87
2×1617.55751.21104913.086
2×2521.68700.7801351161.99
2×3523.911400.5541681401.412
2×5027.615550.3862041660.984
2×7032.421900.2722622040.694
3G1.59.312513.3232433.918
3G2.510.11607.98323220.35
3G412.52604.95444212.624
3G613.73353.3057538.416
3G1016.34901.9178704.87
3×1618.77101.2191752.673
3×2522.910850.780115961.723
3×3525.814600.5541431171.223
3×5029.519750.3861741380.852
3×7035.128550.2722231700.601
3×9538.435650.2062712020.456
4G1.511.418513.3202129.374
4G2.512.32357.98282717.624
4G413.53054.95383510.933
4G615.24053.3049447.288
4G1017.76101.9168584.218
4×1620.89051.2191752.673
4×2525.213350.780115961.723
4×3528.218050.5541431171.223
4×5032.824850.3861741380.852
4×7038.735750.2722231700.601
5G1.512.221013.3202129.374
5G2.513.32757.98282717.624
5G414.93604.95383510.933
5G616.64903.3049447.288
5G1019.67351.9168584.218
5G1622.810751.2191752.673
5G2527.716200.780115961.723
5G3531.021800.5541431171.223
5G5036.430300.3861741380.852
7×1.513.125513.311-33.918
10×1.516.639513.310-33.918
7×2.514.63407.9816-20.35
10×2.518.45257.9814-20.35
12×2.518.95757.9812-20.35
14×2.520.26507.9811-20.35
7×416.34604.9521-12.624
10×420.87354.9519-12.624
12×421.68104.9517-12.624

Manufacturer current ratings to IEC 60364-5-52, one circuit. In air at 40 °C: single core method F, three loaded conductors in trefoil; 2× and 3G method E with two loaded conductors; 3×, 4×, 4G and 5G method E with three loaded conductors; from 7 cores method E with two loaded conductors and the reduction factor of table B.52.17. In the ground: directly buried (method D2) or in conduit (method D1), at 25 °C and a soil thermal resistivity of 2.5 K·m/W; two loaded conductors for 2× and 3G, three for 3×, 4×, 4G and 5G. Voltage drop at cos φ = 1: single-phase for 2×, 3G and from 7 cores, three-phase for all other sizes. Resistance: the IEC 60228 class 5 maximum at 20 °C. A dash means on request.

The complete dimension and current-rating tables are in the datasheet.

Which one do I choose?

RZ1-K (AS) or RV-K?

RZ1-K (AS)

  • green halogen-free sheath
  • class Cca-s1b,d1,a1

RV-K

  • black PVC sheath
  • class Eca

The same flexible construction. RV-K has a black PVC sheath and class Eca; RZ1-K (AS) has a green halogen-free sheath and Cca-s1b,d1,a1. Where the cable is installed permanently in a building and exposed to indoor air, the Bbl requires at least Dca: choose RZ1-K (AS) there.

View RV-K →