BFOU(c) 250 V

NEK 606 offshore fire-resistant instrumentation cable, collective screen

150/250 V NEK TS 606
CU/MGT/EPR/CAM/HFFR/TCWB/SHF2 On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

BFOU(c) 250 V is the fire-resistant instrumentation cable with a collective screen: mica-tape barrier for circuit integrity to IEC 60331, twisted pairs under one overall screen. For emergency and safety instrumentation on platforms and ships. Supplied to order; the lead time is stated in the quote.

BFOU(c) 250 V is a fire-resistant, flame-retardant and halogen-free instrumentation and control cable for fixed installation on offshore units, drilling rigs, FPSOs and ships, designed to NEK TS 606 and IEC 60092-376. The tinned copper conductors carry a mica-tape fire barrier under the halogen-free EPR insulation, are twisted into pairs and protected by a collective screen, a braid of tinned copper wires and a halogen-free, drilling-mud-resistant thermoset outer sheath. The cable maintains circuit integrity under fire conditions and is intended for instrumentation, communication, control, alarm and emergency-system circuits in safe and hazardous areas, including installations exposed to oil, drilling fluids and drilling mud. It is not intended for power distribution.

NEK 606Fire-resistantCollective screen

Also known as: fire-resistant offshore instrumentation cable

Applications

  • Emergency and safety instrumentation that must keep working in a fire.
  • Control, alarm and communication circuits with circuit integrity offshore.
  • Intrinsically safe circuits (blue sheath) in hazardous areas.

What to look out for

  • Circuit integrity to IEC 60331 applies to the cable; brackets, penetrations and terminals must survive the same fire time, or the circuit fails anyway. Metal brackets, no plastic.
  • Without circuit integrity, RFOU(c) suffices and is more cost-effective.
  • If separation between pairs is needed, choose the individually screened (i) version.
Construction
Conductor
Tinned annealed stranded copper, class 2 acc. to IEC 60228. Class 5 (flexible) on request.
Fire barrier
Mica/glass tape applied over the conductor.
Insulation
Halogen-free EPR compound.
Screen
Collective screen over the assembled pairs: copper-laminated polyester tape with tinned copper drain wire.
Armour
Braid of tinned copper wires over a halogen-free inner sheath.
Sheath
Halogen-free, flame-retardant and drilling-mud-resistant thermoset compound (SHF2), grey; blue for intrinsically safe circuits.
Core identification
Pair: black / light blue; pairs progressively numbered.
Electrical & thermal properties
Rated voltage Uo/U
150/250 V (max. operating voltage 300 V).
Test voltage
1.5 kV.
Standard
NEK TS 606; design acc. to IEC 60092-376; conductors acc. to IEC 60228.
Fire-resistant
Circuit integrity acc. to IEC 60331-21.
Flame-retardant
Acc. to IEC 60332-1-2 and IEC 60332-3-22 Cat. A.
Halogen-free
Acc. to IEC 60754-1; low smoke density acc. to IEC 61034-1/-2.
Drilling-mud resistant
Yes, sheath resistant to oil and drilling mud acc. to NEK TS 606.
Max. conductor temperature
+90 °C.
Permitted outer cable temperature, fixed
−20 °C to +90 °C.
Min. bending radius, fixed
6 × outer diameter (8 × outer diameter during installation).
Reaction to fire (CPR)
Outside the scope of EN 50575 (offshore and shipboard cable).
Which one do I choose?

BFOU(c) or BFOU(i)?

BFOU(c) 250 V

  • one collective screen
  • mica tape, IEC 60331-21

BFOU(i)

  • screen per pair or triad
  • mica tape, IEC 60331-21

Both are fire-resistant with a mica tape to IEC 60331-21. BFOU(c) has one collective screen over all pairs, and BFOU(i) its own screen with a drain wire around each pair or triad. Choose BFOU(i) where signals from different circuits must stay separated or each screen is earthed separately, and BFOU(c) when a common screen is sufficient.

View BFOU(i) 250 V →

BFOU(c) 250 V or BFOU 0.6/1 kV?

BFOU(c) 250 V

  • instrumentation cable, 150/250 V
  • measuring, control and alarm signals

BFOU 0.6/1 kV

  • power cable below 1 kV
  • emergency lighting and extinguishing systems

Both keep the circuit working in a fire. BFOU(c) 250 V is the instrumentation cable for 150/250 V, with twisted pairs under a collective screen, for measuring, control and alarm signals. BFOU 0.6/1 kV is the power cable for emergency and safety circuits below 1 kV, such as emergency lighting and fire-extinguishing systems. Signals therefore go over BFOU(c), and power over BFOU 0.6/1 kV.

View BFOU 0.6/1 kV →