Skip to content
Medium voltage

N2XSEYFGbY

Three-core XLPE medium-voltage power cable, copper, flat-steel-wire armoured, 6/10 to 18/30 kV

6/10 to 18/30 kV CPR Fca IEC 60502-2
CU/XLPE/CWS/PVC/FSWA/PVC On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

N2XSEYFGbY is the armoured copper MV cable: flat steel wire armour (FSWA) under a PVC sheath for mechanical protection when buried directly. In all four voltage classes. Supplied to order; the lead time is stated in the quote.

N2XSEYFGbY is a three-core, individually screened, cross-linked polyethylene (XLPE) insulated medium-voltage power cable with galvanised flat-steel-wire armour, for industrial and utility distribution networks. Each copper conductor carries an extruded semi-conductive conductor screen, XLPE insulation, an extruded semi-conductive insulation screen and an individual copper wire screen; the three screened cores are laid up with fillers, covered by an extruded PVC inner sheath, armoured with galvanised flat steel wires bound by a galvanised steel-tape counter helix, and protected by a PVC outer sheath. The armour provides mechanical protection for direct burial and for installation in ground, ducts, cable trenches and industrial plant where additional protection is required. Available from 6/10 to 18/30 kV to IEC 60502-2, constructed following DIN VDE 0276-620.

CopperArmoured (FSWA)Direct burial

Also known as: armoured medium voltage cable

Applications

  • Direct burial where mechanical protection or pressure load applies.
  • Routes with a raised risk of digging or ground-pressure damage.

What to look out for

  • Earth the steel wire armour and copper screen at both ends through the termination; the armour is there for tension and pressure, not as the installation earth.
  • The aluminium counterpart is NA2XSEYFGbY.
Construction
Conductor
Stranded circular (RM) or shaped (SM) plain copper, class 2 acc. to IEC 60228.
Conductor screen
Extruded semi-conductive compound.
Insulation
Cross-linked polyethylene (XLPE), nominal thickness per voltage class (3.4 mm at 6/10 kV, 4.5 mm at 8.7/15 kV, 5.5 mm at 12/20 kV, 8.0 mm at 18/30 kV).
Insulation screen
Extruded semi-conductive compound with a semi-conductive tape.
Core screen
Copper wire screen with a copper equalising/counter tape, applied over each core.
Lay-up
Three screened cores laid up with fillers and a binder tape.
Inner sheath
Extruded polyvinyl chloride (PVC) bedding.
Armour
Galvanised flat steel wires (F) with a galvanised steel-tape counter helix (Gb).
Outer sheath
Polyvinyl chloride (PVC), black (red or other colours on request).
Electrical & thermal properties
Rated voltage Uo/U
6/10 (12) to 18/30 (36) kV.
Test voltage
3.5 × Uo for 5 min (routine test acc. to IEC 60502-2): 21 kV at 6/10, 30.5 kV at 8.7/15, 42 kV at 12/20 and 63 kV at 18/30 kV.
Standard
IEC 60502-2, constructed following DIN VDE 0276-620; conductors acc. to IEC 60228.
Flame-retardant
Acc. to IEC 60332-1-2 (single vertical cable).
Max. conductor temperature
+90 °C (normal operation).
Max. short-circuit temperature
+250 °C (max. 5 s).
Min. bending radius, fixed
15 × outer diameter.
Versions

Voltage classes

Voltage class Uo/UHighest voltage UmInsulation nom.
6/10 kV12 kV3.4 mm
8.7/15 kV17.5 kV4.5 mm
12/20 kV24 kV5.5 mm
18/30 kV36 kV8.0 mm
Which one do I choose?

N2XSEYFGbY or three N2XS(F)2Y?

N2XSEYFGbY

  • one cable, three cores
  • flat steel wire armour
  • PVC inner and outer sheath
  • 6/10 to 18/30 kV

three × N2XS(F)2Y

  • three separate cables
  • unarmoured
  • PE sheath, longitudinally watertight
  • also 20.8/36 kV

N2XSEYFGbY is one cable with three individually screened copper cores, a PVC inner sheath, flat steel wire armour and a PVC outer sheath, from 6/10 to 18/30 kV. Three separate N2XS(F)2Y cables are unarmoured, but longitudinally watertight with a PE sheath, and also come in 20.8/36 kV. If the cable needs mechanical protection when buried directly, choose N2XSEYFGbY. For 20.8/36 kV choose three N2XS(F)2Y.

View N2XS(F)2Y →

N2XSEYFGbY or NA2XSEYFGbY?

N2XSEYFGbY

  • copper conductors
  • smaller cross-section

NA2XSEYFGbY

  • aluminium conductors
  • larger cross-section

The build is the same: three screened cores, flat steel wire armour and PVC sheaths, from 6/10 to 18/30 kV. N2XSEYFGbY has copper conductors, NA2XSEYFGbY aluminium. Aluminium is lighter and more economical, but needs a larger cross-section for the same current. Choose copper where the cable must stay as compact as possible.

View NA2XSEYFGbY →