N2XRH-J

Halogen-free armoured power cable, 0.6/1 kV

0.6/1 kV CPR Eca IEC 60502-1
CU/XLPE/HFFR/GSWA/HFFR On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

N2XRH-J is the halogen-free armoured power cable for 0.6/1 kV: XLPE insulation, galvanised steel wire armour and an HFFR sheath that gives little smoke and no corrosive gases in a fire. For outdoor use, in ducts and for direct burial where both low smoke and mechanical protection are needed. Supplied to order; the lead time is stated in the quote.

N2XRH-J is an armoured power and control cable for 0.6/1 kV, based on IEC 60502-1, for fixed installation indoors, outdoors, in cable ducts and in direct burial where mechanical protection and halogen-free behaviour are required. It has stranded class 2 copper conductors, XLPE insulation, a halogen-free inner covering, a single layer of galvanised round steel wires and a halogen-free, flame-retardant black outer sheath. In a fire the cable emits little smoke and no corrosive halogen gases. The J denotes a green/yellow protective core. Available with 3, 4 and 5 cores, and with three phase cores plus a reduced green/yellow core.

Halogen-freeArmouredDirect burial

Also known as: halogen-free underground cable · halogen-free power cable

Applications

  • Power, utility and lighting supply outdoors, in ducts or direct burial.
  • Routes with a risk of mechanical damage where low smoke also matters.
  • Environments where no corrosive gases may be released in a fire.

What to look out for

  • Halogen-free and low smoke, but flame-retardant, not fire-resistant.
  • Earth the armour at both ends with glands that grip the steel wires; ordinary glands do not.
  • CPR class Eca. Where the cable is exposed to indoor air in a building, the Bbl requires at least Dca. For that we supply N2XRH-J in Dca or Cca on request.
Construction
Conductor
Stranded plain copper, class 2 acc. to IEC 60228.
Insulation
Cross-linked polyethylene (XLPE).
Core identification
Acc. to HD 308: 3G green/yellow, blue, brown; 4G green/yellow, brown, black, grey; 5G green/yellow, blue, brown, black, grey; 3 + 1 brown, black, grey with a reduced green/yellow core.
Inner covering
Halogen-free flame-retardant compound (HFFR), as filler or extruded inner sheath depending on construction.
Armour
Single layer of galvanised round steel wires, with a binder tape over the armour depending on construction.
Outer sheath
Halogen-free flame-retardant compound (HFFR), black.
Electrical & thermal properties
Rated voltage Uo/U
0.6/1 kV.
Test voltage
3.5 kV AC.
Max. conductor temperature
+90 °C.
Max. short-circuit temperature
+250 °C (max. 5 s).
Operating temperature, fixed
−20 °C to +90 °C.
Min. installation temperature
−5 °C.
Min. bending radius
15 × outer diameter.
Standard
Based on IEC 60502-1; conductors acc. to IEC 60228.
Flame propagation
Single cable acc. to IEC 60332-1-2; bunched cables acc. to IEC 60332-3-24, category C.
Smoke density
Acc. to IEC 61034-2.
Halogen-free
Acc. to IEC 60754-1 and IEC 60754-2 (no corrosive gases).
Reaction to fire (CPR)
Eca acc. to EN 50575; Dca and Cca on request.
Dimensions and technical data

Sizes and weights

Cores × mm²R DC 20 °C (Ω/km)Outer Ø approx. (mm)Weight approx. (kg/km)
3G1.512.113.5370
3G2.57.4114.0430
3G44.6115.5510
3G63.0816.5600
3G101.8320.0980
3G161.1522.01260
3G250.72726.01700
3G350.52428.02100
3G500.38731.02700
3G700.26836.53800
3G950.19340.54700
3G1200.15344.55700
3G1500.12450.07300
3G1850.099155.08800
3G2400.075461.511000
3G3000.060168.814814
3G4000.04781.718854
4G1.512.114.0400
4G2.57.4115.0470
4G44.6116.0580
4G63.0818.5830
4G101.8321.01100
4G161.1524.01600
4G250.72728.02200
4G350.52430.52700
4G500.38734.03350
4G700.26840.04800
4G950.19344.06100
4G1200.15350.57800
4G1500.12455.09300
4G1850.099160.511000
4G2400.075468.014000
4G3000.060176.017000
4G4000.04787.023000
5G44.6117.25680
5G63.0819.15864
5G101.8324.01450
5G161.1526.01850
5G250.72731.02750
5G350.52434.03450
5G500.38739.04650
5G700.26844.06100
5G950.19349.08200
5G1200.15355.010000
3×16 + 1×101.15 / 1.8323.01400
3×25 + 1×160.727 / 1.1527.02100
3×35 + 1×160.524 / 1.1529.02400
3×50 + 1×250.387 / 0.72732.53100
3×70 + 1×350.268 / 0.52438.04400
3×95 + 1×500.193 / 0.38742.05600
3×120 + 1×700.153 / 0.26846.56900
3×150 + 1×700.124 / 0.26851.58500
3×185 + 1×950.0991 / 0.19356.510300
3×240 + 1×1200.0754 / 0.15363.513000
3×300 + 1×1500.0601 / 0.12470.515500
3×400 + 1×1850.047 / 0.099180.019500

G = with green/yellow core. In the 3 + 1 sizes the reduced fourth core is the green/yellow core; resistance is given as phase conductor / reduced conductor. Conductor resistance is the IEC 60228 class 2 maximum. Outer diameter and weight differ between constructions and production runs: choose glands with margin. Other sizes on request.

Which one do I choose?

N2XRH-J or VG-YMvKas?

N2XRH-J

  • halogen-free sheaths
  • green/yellow core (the J)
  • CPR class Eca

VG-YMvKas

  • PVC sheaths
  • no green/yellow core
  • CPR class Dca-s2,d2,a3

Both are XLPE cables for 0.6/1 kV with galvanised steel wire armour. N2XRH-J has halogen-free sheaths and a green/yellow core (the J), with CPR class Eca. VG-YMvKas has PVC sheaths and class Dca-s2,d2,a3; there is no green/yellow core, because the earth runs through the earth continuity conductor in the armour. If the cable must give little smoke and no corrosive gases in a fire, choose N2XRH-J; for a Dutch specification, VG-YMvKas.

View VG-YMvKas Dca →

N2XRH-J or BS 6724?

N2XRH-J

  • green/yellow core

BS 6724

  • green/yellow core: five-core only

Both are halogen-free XLPE cables for 0.6/1 kV with galvanised steel wire armour. N2XRH-J has a green/yellow core. On BS 6724 only the five-core version has a green/yellow core; the armour can serve as the circuit protective conductor if its steel cross-section is sufficient. Choose BS 6724 for a British specification; if you want a green/yellow core in a three-core cable, choose N2XRH-J.

View BS 6724 →