H05Z1-K

LSZH insulated flexible wire, halogen-free, 300/500 V

300/500 V CPR Dca EN 50525-3-31
CU/LSZH On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

H05Z1-K is the halogen-free single-core wire for 300/500 V: fine-stranded copper with LSZH insulation that gives little smoke and no corrosive gases in a fire. For panel and cabinet wiring in public buildings. Supplied to order; the lead time is stated in the quote.

H05Z1-K is a harmonised single-core, non-sheathed wire with a flexible plain copper conductor of class 5 and a halogen-free, low-smoke thermoplastic insulation, rated 300/500 V and manufactured in accordance with EN 50525-3-31. It is intended for the internal wiring of switchgear, control panels, distribution boards, luminaires and appliances, and for signalling and control circuits in conduit or trunking, in particular where people, equipment or escape routes must be protected against corrosive gases and dense smoke in the event of fire. The wire is available in the cross-sections 0.5, 0.75 and 1.0 mm² in a range of colours; for 1.5 mm² and larger the 450/750 V type H07Z1-K applies. It is not intended for direct burial, outdoor use without protection, or for continuous flexing in service.

Halogen-freeFlexiblePanel building

Also known as: halogen-free wire

Applications

  • Internal wiring of switch and distribution boards in public buildings.
  • Signal and control circuits in conduit or duct where low smoke is mandatory.
  • Wiring of luminaires and appliances at 300/500 V.

What to look out for

  • Halogen-free and low smoke, but flame-retardant, not fire-resistant.
  • For 1.5 mm² and larger at 450/750 V use H07Z1-K.
  • Fine-stranded (class 5): use ferrules.
Construction
Conductor
Flexible plain annealed copper, class 5 acc. to IEC 60228 / EN 60228.
Insulation
Halogen-free thermoplastic compound type TI7 acc. to EN 50363-7, low smoke emission; no outer sheath (non-sheathed core).
Core colours
Black, blue, brown, grey, white, red, green/yellow; other colours on request.
Electrical & thermal properties
Rated voltage Uo/U
300/500 V.
Test voltage
2,000 V AC.
Standard
EN 50525-3-31 (HD 21.15); insulation compound acc. to EN 50363-7; conductors acc. to IEC 60228 / EN 60228.
CPR classification
Dca-s2,d2,a2 (EN 50575, halogen-free); B2ca-s1a,d1,a1 on request.
Flame-retardant
Acc. to EN 60332-1-2 / IEC 60332-1-2.
Halogen-free
Acc. to EN 60754-1 / IEC 60754-1 and EN 60754-2 / IEC 60754-2; low smoke density acc. to EN 61034-2 / IEC 61034-2.
Conductor standard
IEC 60228 / EN 60228, class 5 (flexible).
Max. conductor temperature
+70 °C (max. +150 °C for 5 s in short circuit).
Permitted surface temperature, fixed
0 °C to +70 °C (min. +5 °C during installation).
Min. bending radius, fixed
4 × outer diameter.
Which one do I choose?

H05Z1-K or H05V-K?

H05Z1-K

  • halogen-free insulation

H05V-K

  • PVC insulation

Both are fine-stranded wires for 300/500 V and 70 °C, in 0.5 to 1 mm² inclusive. H05V-K has PVC insulation, H05Z1-K halogen-free insulation that gives little smoke and no corrosive gases in a fire. Choose H05Z1-K for enclosure and panel wiring where the specification calls for halogen-free; otherwise H05V-K is sufficient.

View H05V-K →

H05Z1-K or H07Z1-K?

H05Z1-K

  • 300/500 V
  • 0.5, 0.75 and 1 mm²

H07Z1-K

  • 450/750 V
  • from 1.5 mm²

It is the same halogen-free wire family in two voltage ratings. H05Z1-K is for 300/500 V and is available in 0.5, 0.75 and 1 mm²; H07Z1-K is for 450/750 V and starts at 1.5 mm². H05Z1-K is used for wiring enclosures, luminaires and appliances. For installation wire in conduit or trunking, choose H07Z1-K.

View H07Z1-K →