Skip to content
Bus cables

RS-485 1×2×0.22 SWA PVC

RS-485 bus cable, 1 pair 0.22 mm², 120 Ω, foil and tinned-copper braid, steel wire armoured, PVC sheath

300 V CPR Eca EIA/TIA-485
CU/PE/CAM/TCWB/PVC/GSWA/PVC On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

RS-485 1×2×0.22 SWA PVC is the armoured one-pair bus cable: 120 Ω, foil plus tinned-copper braid, a PVC inner sheath, steel wire armour and a grey PVC outer sheath. Supplied to order; the lead time is stated in the quote.

RS-485 1×2×0.22 SWA PVC is an RS-485 (EIA/TIA-485) data bus cable with a characteristic impedance of 120 Ω, for serial fieldbus communication between PLCs, drives, operator panels, meters and SCADA/RTU equipment. One twisted pair of stranded tinned-copper conductors with polyethylene (PE) insulation is enclosed by an overall screen of aluminium foil with a tinned-copper drain wire and a tinned-copper braid, which keeps the bus reliable in electrically noisy installations and over long distances. A black PVC inner sheath, a steel wire armour for mechanical protection and a grey PVC outer sheath complete the cable.

RS-485Bus cableArmoured

Also known as: RS485 cable · Modbus cable · fieldbus cable

Applications

  • RS-485 in industry and on sites where the cable is at risk of impact.
  • Bus links along cable trays and machinery with a risk of mechanical damage.

What to look out for

  • CPR class Eca. Where the cable is exposed to indoor air in a building, the Bbl requires at least Dca.
  • The outer diameter is 10.20 mm (±0.50 mm). Choose a gland for armoured cable, which clamps the steel wire armour.
Construction
Conductor
Stranded tinned copper, 7 × 0.20 mm (±0.008 mm), approx. 0.22 mm².
Insulation
Polyethylene (PE), nominal diameter 1.80 mm (±0.13 mm).
Pair
One twisted pair; colours white/blue and blue/white.
Screen
Overall aluminium foil with a stranded tinned-copper drain wire, 7 × 0.20 mm.
Braid
Tinned copper, 112 × 0.12 mm.
Inner sheath
Polyvinyl chloride (PVC), black, nominal diameter 5.89 mm (±0.20 mm).
Armour
Steel wire armour (SWA), 26 wires of 0.90 mm.
Outer sheath
Polyvinyl chloride (PVC), grey.
Cross-reference
Comparable to Belden 9841 (RS-485, 1 pair), with an added PVC inner sheath and steel wire armour.
Electrical & thermal properties
Rated voltage
300 V.
Characteristic impedance
120 Ω.
Conductor resistance
max. 85 Ω/km at 20 °C.
Temperature range
−30 °C to +80 °C.
Compliance
RoHS (EU 2015/863) and REACH.
Reaction to fire (CPR)
Eca (EN 50575).
Dimensions and technical data

Key figures

Pairs × mm²Outer Ø (mm)Impedance (Ω)R 20 °C (Ω/km)
1×2×0.2210.20 ±0.50120max. 85

Manufacturer's nominal values for this construction, with the tolerances from the sheet. Weight and minimum bending radius on request. Belden is a trademark of Belden Inc.; the name is used for comparison only.

Which one do I choose?

Armoured or PE UV?

RS-485 1×2×0.22 SWA PVC

  • steel wire armour
  • Ø 10.20 mm

RS-485 1×2×0.20 PE UV

  • unarmoured
  • Ø 5.90 mm

Under its grey PVC outer sheath, the SWA version has steel wire armour against mechanical damage, and it is 10.20 mm thick. The PE version is unarmoured, 5.90 mm thick and has a UV-resistant sheath. If there is a risk of mechanical damage, choose the armoured version.

View RS-485 1×2×0.20 PE UV →

RS-485 cable or PROFIBUS DP cable?

RS-485 1×2×0.22 SWA PVC

  • 120 Ω
  • for Modbus RTU among others

PROFIBUS DP cable

  • 150 Ω (type A)
  • for PROFIBUS DP

PROFIBUS DP also uses RS-485, but requires a 150 Ω cable (type A to IEC 61158). This cable has 120 Ω and is intended for buses such as Modbus RTU. For PROFIBUS DP you therefore choose a PROFIBUS cable.