RS-485 1×2×0.20 LSZH

RS-485 bus cable, 1 pair 0.20 mm², 120 Ω, foil and tinned-copper braid, LSZH sheath

300 V CPR Eca EIA/TIA-485
CU/PE/CAM/TCWB/LSZH On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

RS-485 1×2×0.20 LSZH is the screened bus cable with one pair: 120 Ω, foil plus tinned-copper braid and a grey halogen-free sheath. Supplied to order; the lead time is stated in the quote.

RS-485 1×2×0.20 LSZH is an RS-485 (EIA/TIA-485) data bus cable with a characteristic impedance of 120 Ω, for serial fieldbus communication between PLCs, drives, operator panels, meters and SCADA/RTU equipment. One twisted pair of stranded tinned-copper conductors with polyethylene (PE) insulation is enclosed by an overall screen of aluminium/polyester (Al/PET) foil with a tinned-copper drain wire and a tinned-copper braid, which keeps the bus reliable in electrically noisy installations and over long distances. The grey sheath is a low-smoke zero-halogen (LSZH) compound.

RS-485Bus cableLSZH

Also known as: RS485 cable · Modbus cable · fieldbus cable

Applications

  • Modbus RTU and other serial RS-485 buses between PLC, drive and meter.
  • Bus links in control cabinets and installations with a lot of interference.

What to look out for

  • CPR class Eca. Where the cable is exposed to indoor air in a building, the Bbl requires at least Dca; choose RS-485 1×2×0.22 LSZH B2ca (110 Ω) there.
  • Terminate the bus at both ends with 120 Ω, equal to the impedance of the cable.
Construction
Conductor
Stranded tinned copper, 7 × 0.19 mm (±0.008 mm), approx. 0.20 mm².
Insulation
Polyethylene (PE), nominal diameter 1.80 mm (±0.13 mm).
Pair
One twisted pair; colours white/blue and blue/white.
Screen
Overall aluminium/polyester (Al/PET) foil with a stranded tinned-copper drain wire, 7 × 0.19 mm.
Braid
Tinned copper, 112 × 0.12 mm, coverage 90%.
Sheath
Low-smoke zero-halogen (LSZH) compound, grey.
Cross-reference
Comparable to Belden 9841 (RS-485, 1 pair). Differs in sheath (LSZH instead of PVC) and conductor (7 × 0.19 mm instead of 7 × 0.20 mm).
Electrical & thermal properties
Rated voltage
300 V.
Characteristic impedance
120 Ω.
Mutual capacitance
42 pF/m (conductor to conductor).
Conductor resistance
max. 95 Ω/km at 20 °C.
Temperature range
−30 °C to +80 °C.
Compliance
RoHS (EU 2015/863) and REACH.
Reaction to fire (CPR)
Eca (EN 50575).
Dimensions and technical data

Key figures

Pairs × mm²Outer Ø (mm)Impedance (Ω)R 20 °C (Ω/km)
1×2×0.205.90 ±0.20120max. 95

Manufacturer's nominal values for this construction, with the tolerances from the sheet. Weight and minimum bending radius on request. Belden is a trademark of Belden Inc.; the name is used for comparison only.

Which one do I choose?

One or two pairs?

RS-485 1×2×0.20 LSZH

  • one pair
  • Ø 5.90 mm

RS-485 2×2×0.20 LSZH

  • two pairs, also for four-wire
  • Ø 6.80 mm

For a two-wire bus (half duplex) you use one pair. The second pair is for four-wire RS-485 (full duplex), with a separate pair for transmit and receive, or for the signal reference (common) that many devices ask for. Screen, impedance and sheath are otherwise the same. The one-pair cable is 5.90 mm thick, the two-pair cable 6.80 mm.

View RS-485 2×2×0.20 LSZH →

Eca or B2ca?

RS-485 1×2×0.20 LSZH

  • CPR Eca
  • 120 Ω

RS-485 1×2×0.22 LSZH B2ca

  • CPR B2ca-s1a,d0,a1
  • 110 Ω ±15 Ω

Both are halogen-free. This version is Eca. Where the cable is exposed to indoor air in a building, the Bbl requires at least Dca, and then you choose the B2ca version. It has 110 Ω ±15 Ω instead of 120 Ω, HDPE insulation, a blue UV-resistant sheath and a rated voltage of 600 V.

View RS-485 1×2×0.22 LSZH B2ca →