Skip to content
Installation cables

H07Z1-R

LSZH insulated stranded wire, halogen-free, 450/750 V

450/750 V CPR Cca EN 50525-3-31
CU/LSZH On request Lead time: On request; the lead time is stated in the quote. Send your enquiry
Application

H07Z1-R is the halogen-free stranded single-core wire for 450/750 V: class 2 copper with LSZH insulation, from 1.5 to 400 mm². The stranded conductor makes the large sizes easier to handle than solid. For fixed installation in conduit, duct and distribution boards in buildings where many people gather. Supplied to order; the lead time is stated in the quote.

H07Z1-R is a harmonised single-core, non-sheathed wire with a stranded plain copper conductor of class 2 and a halogen-free, low-smoke thermoplastic insulation, rated 450/750 V and manufactured in accordance with EN 50525-3-31 (Type 2). It is intended for fixed installation in surface-mounted or recessed conduit, trunking or closed installation ducts, and for protected fixed wiring inside lighting fittings, switchgear and control equipment, in buildings where many people gather and the emission of smoke and corrosive gases in the event of fire must be limited. The wire is available from 1.5 to 400 mm² in a range of colours, with 500 and 630 mm² on request. It is not intended for direct burial, outdoor use without protection, or for flexing in service.

Halogen-freeStrandedDistribution board

Also known as: halogen-free wire · stranded wire

Applications

  • Fixed installation in conduit, trunking or duct in buildings where halogen-free wire is specified.
  • Large cross-sections up to 400 mm², where a stranded conductor is easier to lay than solid.
  • Protected fixed wiring in switchgear and distribution boards.

What to look out for

  • Halogen-free and low smoke, but flame-retardant, not fire-resistant.
  • Stranded (class 2) is stiffer than fine-stranded; for wiring with many bends in an enclosure choose H07Z1-K.
  • Non-sheathed wire: install it in conduit or duct.
Construction
Conductor
Stranded plain annealed copper, class 2 acc. to IEC 60228 / EN 60228.
Insulation
Halogen-free thermoplastic compound type TI7 acc. to EN 50363-7, low smoke emission; no outer sheath (non-sheathed core).
Core colours
Black, blue, brown, grey, white, red, green/yellow; other colours on request.
Electrical & thermal properties
CPR classification
Cca-s1,d2,a1 (EN 50575, halogen-free); B2ca-s1,d1,a1 on request.
Rated voltage Uo/U
450/750 V.
Test voltage
2,500 V AC.
Standard
EN 50525-3-31, Type 2 (HD 21.15); insulation compound acc. to EN 50363-7; conductors acc. to IEC 60228 / EN 60228.
Flame-retardant
Acc. to EN 60332-1-2 / IEC 60332-1-2; flame spread of bunched cables acc. to EN 60332-3-24 / IEC 60332-3-24 (Type 2).
Halogen-free
Acc. to EN 60754-1 / IEC 60754-1 and EN 60754-2 / IEC 60754-2; low smoke density acc. to EN 61034-2 / IEC 61034-2.
Conductor standard
IEC 60228 / EN 60228, class 2 (stranded).
Max. conductor temperature
+70 °C (max. +150 °C for 5 s in short circuit).
Permitted surface temperature, fixed
−10 °C to +70 °C (min. +5 °C during installation).
Min. bending radius, fixed
6 × outer diameter.
Dimensions and technical data

Sizes and weights

Cross-section (mm²)Outer Ø approx. (mm)Weight approx. (kg/km)R DC 20 °C (Ω/km)
1.52.92212.1
2.53.6337.41
44.1474.61
64.6663.08
105.91101.83
166.81691.15
258.32600.727
359.43500.524
5011.04720.387
7012.56650.268
9514.69130.193
12016.211600.153
15018.014200.124
18520.017600.0991
24022.723200.0754
30025.829220.0601
40029.337600.047

500 and 630 mm² on request.

Which one do I choose?

H07Z1-R or H07Z1-K?

H07Z1-R

  • stranded (class 2)

H07Z1-K

  • fine-stranded (class 5)

Both are non-sheathed halogen-free wires for 450/750 V and 70 °C. H07Z1-R has a stranded conductor (class 2) for fixed runs, H07Z1-K a fine-stranded one (class 5) that bends more easily. Choose H07Z1-K for wiring in enclosures with many bends; for fixed runs in conduit and duct H07Z1-R is sufficient.

View H07Z1-K →

H07Z1-R or H07V-R?

H07Z1-R

  • halogen-free insulation

H07V-R

  • PVC insulation

Both are non-sheathed stranded wires for 450/750 V and 70 °C. H07V-R has PVC insulation; H07Z1-R has halogen-free insulation that gives little smoke and little corrosive gas in a fire. Choose H07Z1-R where the specification calls for halogen-free wire; otherwise H07V-R is sufficient.

View H07V-R →

H07Z1-R or H07Z1-U?

H07Z1-R

  • stranded (class 2)

H07Z1-U

  • solid (class 1)

Both are non-sheathed halogen-free wires for 450/750 V and 70 °C. H07Z1-R has a stranded conductor (class 2), H07Z1-U a solid one (class 1). Solid wire sits firmly in the terminal, but becomes awkward to lay in the larger cross-sections. For those, choose H07Z1-R; in the small cross-sections H07Z1-U is the usual choice.

View H07Z1-U →